Overcurrent Protection for Railway Applications

SPRECON-E-P RS6

The modular SPRECON-E-P RS..6 railway overcurrent protection devices are used in railway systems and grids as main or backup protection for switching and catenary systems. The implemented protection functions enable the selective protection of single- or double-sided fed catenary feeders. In addition, the devices can be used as system protection for railway switchgear or as backup protection for railway lines or transformers.

 

Areas of Application

Thanks to the extensive additional functions, the devices are particularly qualified for the following areas of application with different grid frequencies (16.7 Hz, 25 Hz, 50 Hz):

  • AC catenary systems in single or two-wire applications
  • Switchgear for catenary feeders
  • Railway transformers or lines 
  • Connection of auxiliary consumers to the railway grid

 

Operation & Parameter Setting

The detached control panel enables efficient and safe operation. You can use it to carry out the necessary operating actions as well as the complete protection setting on site.

The SPRECON-E control system is configured with the SPRECON-E Designer. Using the drag & drop function, you can configure the control system functions quickly and easily. The integrated Display Editor creates all images for the SPRECON control panel in parallel. This displays process and device information in full graphics and colour on a large LC display. In addition, freely configurable LEDs are available for signalling.

With the autonomous navigation keys, you can move intuitively through the various display pages and submenus and use the extensive protection and control technology functions.

 

The multifunctional SPRECON-E-P RS..6-2 overcurrent protection devices have a modular design and are equipped with standardised hardware modules. The implemented protection functions enable selective main or backup protection of single- or autotransformer catenary feeders. It can also be used as system protection for railway switchgear or as backup protection for railway lines or transformers. In addition to protection and measured value recording, you can also control circuit breakers with the devices.

 

Protection Packages

You can optionally include additional protection functions as extension packages to the standard basic range of functions. The system protection functions available in some protection packages are implemented as independent protection functions in the firmware.

  • Package 1: Non-directional railway overcurrent protection
  • Package 2: Directional railway overcurrent protection
  • Package 3: Package 2 + Synchro-Check 

In addition, SPRECON-E-P RS..6-2 devices can perform further tasks such as voltage, frequency and power direction protection.

 

Separated Protection & Control Technology

The SPRECON-E-P RS..6-2 multifunctional devices ensure the protection of electrical equipment and can simultaneously take over control and monitoring tasks in railway power systems. The devices fulfil all secondary tasks and are characterised by a consistent separation of the protection and control technology parts:

  • Separated data models
  • Separated control and protection firmware
  • Separated control and protection configuration
  • Separated passwords
  • No testing of protection function at feeder nor primary circuit disconnection required on updating control parameters or firmware

By dividing them into protection configuration and control technology parameterisation, the devices meet the different requirements in the best possible way and can be used in any switchgear panel, taking into account user-specific requirements.

 

Configuration

You can activate or deactivate all functions individually depending on the application. You simply hide functions that are not required. The configuration of the device thus remains simple and clear. In the control technology, the focus is on the concept of a database-supported type orientation according to the same bay types. This significantly simplifies and facilitates the project planning of extensive systems.

 

Implemented
Protection Functions
REFERENCE TYPE
IEC
61850-7-4
RS6
4 x I
4 x U
RSR6
4 x I
4 x U
RSRY6
4 x I
4 x U
Overcurrent Protection for Railway Applications          
I> DT/IDMT, 6 stages 50, 51 PIOC, PTOC
Fast tripping
I> H DT, 1 stage
50, 51 PIOC, PTOC
Switch-on protection 50 PIOC, PTOC
Inrush stabilisation (Inrush restraint)   PHAR
Short circuit direction detection 67 PTOC, RDIR  
Overvoltage protection
U>, 3 stages
59 PTOV  
Undervoltage protection
U<, 3 stages
27 PTUV  
Frequency protection
f<, 4 stages; f>, 2 stages
81 PTOF, PTUV  
Frequency change protection (ROCOF)
df/dt falling, 4 stages,
df/dt rising, 2 stages
81R PFRC  
Directional power protection (P, Q) 2 stages each 32 PDOP, (PDUP)  
Overload protection
with optional redundant coolant temperature detection
49 PTTR
Reclosing lockout 86 PMRI
Circuit breaker failure protection (CBF) 50BF PTOC, RBRF
Synchrocheck 25 RSYN    
CB TRIP by external signal 81 (PTRC)
CB control in protection device    
Fault locator (FL) 21FL RFLO  
Pulse shaper stage (programmable logic)
6 configurable functions
   
Trip circuit supervision, 2 inputs (2x) 74TC  
Parameter sets     8 8 8
Logic + time stages for digital inputs    
Virtual binary inputs/control inputs     30/15 30/15 30/15
Logic + hold time for output relays    
Measurands, short report    
Event logging, non-volatile   RDRE
Disturbance data recording, non-volatile RADR, RBDR  
Statistics    
Measurand checks    
Self supervision    
Assistance for testing and commissioning    

Dimensions & Weight

  • Dimensions: 212/436 x 176 x 257 mm (W x H x D) incl. connections
  • Weight: < 6 kg

General Functions

  • Remote maintenance and configuration
  • Time synchronisation: binary input (impulse), serial (DCF77) or via Ethernet (NTP, PTP)
  • GPS, station and remote control
  • Diagnosis via webserver
  • AI modules for overload protection available
  • AO modules for combined devices available
  • CP with a fully graphical display with 3-coloured LEDs
  • Automatic backup on SD card
  • Redundant power supply as option

Communication

  • IEC 60870-5-103/-104, IEC 61850
  • RS232, RS422/485, fibre optic, 10/100 Mbit Ethernet
  • 2 additional optical Ethernet interfaces for redundant ring
  • Connection via leased or dialup line
  • Integration of stand-alone devices via station bus

Additional Protection Functions

  • High-current stage (catenary protection with short circuit function)
  • Tank/switchgear protection (separated monitoring function for switchyard applications)
  • Separation of protection event recording from control data
  • Nominal current selection (1/5 A) via terminal connection
  • Settings via control panel and PC through menu-assisted plain text messaging

Control Functions

  • Control and monitoring of switching devices and process elements
  • Freely programmable logic (PLC)
  • Control of transformer tap changers and Petersen coil
  • Power output with high breaking capacity (optional)
  • Limit value monitoring
  • Maximum value calculation (non-return pointer)
  • Metered value capturing, operating hours counter, switching operations counter
  • ...

 